Fume Cupboard Technical Data Sheet FHS-1
Fixed fume cupboard designed manufactured to DFEE Building Bulletin 88.
For educational establishments can also be manufactured to BS 7258 for research.
Standard colours; Grey, white. Non stock colours to order.
Cupboards installed in island or peninsular situations have clear glass back and baffles for all round vision.
Standard Specification
| Exterior | Epoxy coated framework with shaped front fascia having secondary air inlet grille above sash and low level air inlet below sill. |
| Interior | 6mm White solid grade laminate rear, top and back panels having silicone sealed joints and removable back baffles. |
| Workbase | Dished solid epoxy resin with cutout for drip cup. We suggest fitting small sink for cupboards in prep rooms. |
| Sash | 6mm frameless toughened glass hung on stainless steel cables over nylon ballraced pulleys with single counter weight. Sash fitted with full length profiled handle with rise set to stop at 400mm. working height. |
| Services | 1no panel mounted valve with cold water swanneck outlet. 1no panel mounted safety gas valve with bench outlet. 1no oval vulcathene 497 drip cup. 1no twin 13amp switched socket outlet. 1no switched fused spur for twin fluorescent luminaire. |
| Supported By | Fixed storage cupboard. |
| Options | Epoxy coated mild steel tableframe, push under storage, ventilated storage kit.
Airflow monitor,fan starter,solid grade Trespa workbase. |

| STANDARD STOCK SIZES AND DUCT CONNECTIONS.
|
Model FHS/10 1000mm. wide @ min 0.3m/s = 200mm dia’ connection. Model FHS/12 1200mm. wide @ min 0.3m/s = 200mm dia’ connection. Model FHS/15 1500mm. wide @ min 0.3m/s = 250mm dia’ connection. Model FHS/20 2000mm. wide @ min 0.3m/s = 315mm dia’ connection. Non standard sizes to order. |
SERVICE CONNECTIONS.
Gas and water panel valves terminate with flexible at rear of cupboard in 1/4” m/i thread at 750mm high off floor.
Waste from drip cup or sink terminates with a 38mm outlet.
Socket and light fitting internally wired to a 100mm junction box below cupboard ready for connection to supply by others.
Separate circuit required for fan control having means of isolation at cupboard and fan motor.
INSTALLATION SERVICES AVAILABLE; EXTRACT SYSTEMS, PLUMBING, CONTROL WIRING, AIR MAKE-UP SYSTEMS AND ASSOCIATED BUILDING WORKS.